CLONE(8)
========

NAME
----

clone - Clone an UPS, treating its outlet as if it were an UPS
        (with shutdown INSTCMD support)

SYNOPSIS
--------

*clone* -h

*clone* -a 'UPS_NAME' ['OPTIONS']

NOTE: This man page only documents the specific features of the
clone driver.  For information about the core driver, see
linkman:nutupsdrv[8].

DESCRIPTION
-----------

This driver, which sits on top of another driver's local UNIX socket file
(or Windows named pipe), allows users to group clients to a particular
outlet of a device and deal with this output as if it were a normal UPS.

Unlike the linkman:clone-outlet[8] driver, this driver represents a
manageable device that can be used both for monitoring and for client
computer and UPS/ePDU outlet shutdowns (it supports sending relevant
instant commands during run time).

Unlike linkman:dummy-ups[8], this driver does not require a running `upsd`
data server nor use the networked NUT protocol to talk to the "real" driver
(which may be remote in case of `dummy-ups` repeater mode).

This driver does not create a completely new virtual device, but replaces or
extends some of the original readings reported by the "real" driver using
information from the specified outlet, and relays all other readings as they
were.

Remote clients like `upsmon` can `MONITOR` the device entry presented by the
data server with this driver (and the "real" driver) running and published.

A larger deployment with one or more lower-priority devices collected on a
manageable outlet of an UPS or ePDU would likely see several drivers set
up on the system actually capable of interactions with the UPS and running
the NUT data server linkman:upsd[8] (and likely powered by another outlet):

* a "real" driver talking to the UPS;
* a `clone` driver talking to the "real" driver and issuing outlet power-off
  (or power-cycle) based on relatively high thresholds for remaining battery
  charge and/or runtime of the actual UPS (or explicit instant commands),
  with such operations first setting the respective timers for the outlet
  on the "real" driver, and the "FSD" flag among states of the virtual UPS
  status;
* possibly a `clone-outlet` driver which is read-only and interprets the
  outlet timer values as triggers for "FSD" or "OFF" flags reported among
  states of the virtual UPS status.

With this approach, the lower-priority systems collected on such outlet
would run the NUT linkman:upsmon[8] client to `MONITOR` the virtual UPS
presented by the read-only `clone-outlet` driver and shut down as soon as
the "FSD" flag is raised (fairly early, based on charge and/or runtime
thresholds configured for that driver) allowing the higher-priority devices
(likely including the NUT server) to enjoy a longer on-battery life.

The `clone` driver responsible for outlet power state changes would not
normally be monitored directly (e.g. to avoid unfortunate direct shutdown
requests from those clients), although it can be (instead of `clone-outlet`)
in sufficiently trusted networks.

EXTRA ARGUMENTS
---------------

This driver supports the following settings:

*port*='drivername-devicename'::
Required. The standard NUT driver `port` setting, here it provides the name
of the local Unix socket file (or Windows named pipe) for connection to the
"real" device driver.

*load.off*='command'::
Recommended.  Set the command on the "real" UPS driver that will be used to
switch off the outlet.  You need both *load.off* and *load.on* in
order to power cycle the outlet.  Otherwise, shutting down the clients
powered by an outlet is a one way street (see <<_important,IMPORTANT>>).

*load.on*='command'::
Recommended.  Set the command on the "real" UPS driver that will be used to
switch on the outlet.  You need both *load.off* and *load.on* in
order to power cycle the outlet.  Otherwise, shutting down the clients
powered by an outlet is a one way street (see <<_important,IMPORTANT>>).

*load.status*='value'::
Recommended.  Set the variable on the "real" UPS driver that will be used
to indicate the outlet status (i.e. on/off).  If not specified, the clone
driver will attempt to keep track of the outlet status, but this is less
reliable.

*offdelay*='num'::
Set the timer (in seconds) before the outlet is turned off after the
shutdown condition (+OB LB+) for this outlet is met or a command to shutdown
was issued.  Defaults to 120 seconds.

*ondelay*='num'::
Set the timer (in seconds) for the outlet to switch on in case the power
returns after the outlet has been switched off.  Defaults to 30 seconds.

*mincharge*='value'::
Set the remaining battery level when the clone UPS switches to LB
(percent).

*minruntime*='value'::
Set the remaining battery runtime when the clone UPS switches to LB
(seconds).

IMPLEMENTATION
--------------

The port specification in the linkman:ups.conf[5] should reference the
local driver socket (or Windows named pipe) that the "real" UPS driver
is using. For example:

------
  [realups]
     driver = usbhid-ups
     port = auto

  [clone-outlet-1]
     driver = clone
     port = usbhid-ups-realups
     load.on = outlet.1.load.on
     load.off = outlet.1.load.off
     load.status = outlet.1.status
     desc = "Outlet 1 of the Real UPS"
     [...]
------

This driver supports instant commands to initiate a forced shutdown for
`upsmon` or similar clients which `MONITOR` this virtual UPS device, if
the outlet status is currently 'on' and no other shutdown was initiated
yet (setting the virtual UPS shutdown delay timer to `offdelay` and
issuing an FSD via `ups.status`):

* `shutdown.return` -- power the outlet back on after `ondelay`;
* `shutdown.stayoff` -- keep the outlet 'off'.

Such commands are propagated to the "real" driver using the NUT socket
protocol (using command names specified in the `load.off` and `load.on`
driver configuration options), if the shutdown or start timers are set
at the moment, or if the "real" device is not "online" and its known
battery charge or runtime are below the configured "low" thresholds.

The outlet status is determined using the name specified by the
`load.status` driver option if set, or is just assumed by latest
completed shutdown/start operation (using unknown outlet number).

The driver does not support a common NUT device shutdown operation as
such (`clone -k` just prints an error and bails out).

This driver also supports setting certain NUT variables at run-time:

* `battery.charge.low` -- see `mincharge` in driver options;
* `battery.runtime.low` -- see `minruntime` in driver options.

Compared to the "real" driver's readings, this driver also adds
(or overrides) the following data points: `ups.delay.shutdown`,
`ups.delay.start`, `ups.timer.shutdown` and `ups.timer.start`.
It keeps track of "real" driver's values of `battery.charge` and
`battery.runtime` (actual current readings) to decide on automated
outlet shutdown later on.

IMPORTANT
---------

Unlike a real UPS, you should *not* configure a upsmon primary mode for this
driver.  When a linkman:upsmon[8] primary sees the `OB LB` flags and tells the
linkman:upsd[8] data server that it is OK to initiate the shutdown sequence,
the server will latch the FSD status, and it will not be possible to restart
the systems connected without restarting the `upsd` server.

This will be a problem if the power returns after the clone UPS initiated
the shutdown sequence on its outlet, but returns before the real UPS begins
shutting down. The solution is in the `clone` driver itself, that will insert
the FSD flag if needed without the help of an upsmon primary.

CAVEATS
-------

The clone UPS will follow the status on the real UPS driver.  You can only
make the clone UPS shutdown earlier than the real UPS driver, not later.
If the real UPS driver initiates a shutdown, the clone UPS driver will
immediately follow.

Be aware that the commands to shutdown/restart an outlet on the real UPS
drivers are not affected, so if you tell the real UPS driver to shutdown
the outlet of the clone UPS driver, your clients will lose power without
warning.

If you use service management frameworks like systemd or SMF to manage the
dependencies between driver instances and other units, then you may have
to set up special dependencies (e.g. with systemd "drop-in" snippet files)
to queue your `clone` drivers to start after the "real" device drivers.

//////////////////////////////////////
TODO later: declare the driver as "optional", see
https://github.com/networkupstools/nut/issues/1389
//////////////////////////////////////

AUTHOR
------

Arjen de Korte <adkorte-guest@alioth.debian.org>

SEE ALSO
--------

linkman:upscmd[8],
linkman:upsrw[8],
linkman:ups.conf[5],
linkman:clone-outlet[8],
linkman:nutupsdrv[8]

Dummy driver:
~~~~~~~~~~~~~

The "repeater" mode of 'dummy-ups' driver is in some ways similar to the
'clone' and 'clone-outlet' drivers, by relaying information from a locally
or remotely running "real" device driver (and NUT data server).

linkman:dummy-ups[8]

Internet Resources:
~~~~~~~~~~~~~~~~~~~

The NUT (Network UPS Tools) home page: https://www.networkupstools.org/